Our Mission Statement
NOJA Power provide high quality, quality assured medium voltage recloser related products and services to an international market. Use the links below to explore our available products.
News 2011
2011 March NOJA Power Commissioned to Supply Switchboard For Airport Link Project
News 2010
2010 December NOJA POWER Expands its Type Testing Capabilities
2010 November NOJA POWER Environmental Management System ISO14001 Certified
2010 July NOJA Power elevated to National Master Electrician Status
2010 June NOJA Power OSM38 KEMA Type Testing Completed
2010 March NOJA Power Motor Control Centres Empowers Queensland Coal Export
2010 March NOJA Power Auto Recloser Perfect Solution for Sectionalising
2010 March NOJA Power Low Voltage Motor Control Centres, Specify for Safety, Reliability and Performance
2010 June NOJA POWER OSM38 KEMA Type Testing Completed
2010 Febuary TELUS and OSM Recloser Provide Smart Grid Solution
2010 January NOJA Power Auto Recloser Operating Smart Grids Below Freezing
News 2009
2009 October NOJA Power Winner of the 2009 Premier of Queensland's Exporter of the Year Award
2009 August Trade Queensland International Business Cadetship Successfully Completed
2009 August Kanban & Lean Manufacturing Improve Productivity
2009 August NOJA Power OSM27 Type Tested at KEMA
2009 August NOJA Power New Corporate Office and Factory
2009 Feburary NOJA Power Reclosers to Increase Distribution Network Reliability in Brazil
2009 Feburary Powerco Successfully Commissions Automatic Backfeed Restoration Scheme
2009 Feburary NOJA Power Continues to Supply MCCs for Abbot Point Coal Export Upgrade
News 2008
2008 November ENERGEX Awards NOJA Power a Recloser Supply Contract as Part of Network Upgrade Program
2008 September Factory Expansion Increases Production Capabilities
2008 August Practical Perspective on Recloser Training
2008 August NOJA Powers Brisbane Clem Jones Tunnel
2008 June NOJA Power Commended on Manufacturing Endeavours
2008 June OSM Reclosers helps Mine through Bat Season
2008 May NOJA Power exhibits OSM Recloser reliability at IEEE Conference
2008 April NOJA Power Awarded for Exporting Success
2008 April Brazilian Intern Graduates & Joins NOJA Power Distributor
2008 March NOJA Power Teams up to Supply PNG Power
2008 March Solid-Dielectric ACR Installation Improves Distribution Network Reliability
2008 Feburary NOJA Power to Exhibit at Upcoming IEEE PES Conference & Exhibition
News 2007
2007 October NOJA Power Switchgear Pty Ltd Appoints Exclusive Distributor for the Territory of New Zealand
2007 September Fiji Electricity Authority Contract Award
2007 September ENERGEX Reaps Benefits of OSM Installations
2007 August Planning for the future: Water Matters
2007 August ETSA Utilities Award 5 Year Supply Contract
2007 August NOJA Power & Comulsa exhibit at Exponor Conference, Chile
2007 January Gold Coast Airport upgrades using OSM Recloser
News 2006
2006 November NOJA Power receives AEEMA Excellence in Exporting Award 2006
2006 November Trinidad & Tobago Electricity take delivery of NOJA Power OSM Reclosers
2006 September NOJA Power welcomes new member to sales team
2006 August Fiji Electricity Authority Remote Controls NOJA Power Reclosers
2006 July New Shipment to Bangladesh
2006 June A Global Bank to Support A Global Business
2006 June Motor control centres come as standard
2006 June Standard design for motor control centres improves quality
2006 August Fiji Electricity Authority Remote Controls NOJA Power Reclosers
2006 May Think Motor Control Centres - Think NOJA Power
2006 May 132kV Substation Protection and SCADA control project
2006 May Reliable power thanks To NOJA Power reclosers
2006 May Live line work: Is your switchgear fault contained?
Reliable Power At Western Australian Mine Thanks To NOJA Power Reclosers
Kimberley Nickel's Sally Malay mine in Western Australia have dramatically improved their power quality after installing two NOJA Power reclosers in their distribution network. This eliminated frequent and lengthy power outages from affecting their entire network. These conditions are now reduced to short outages in isolated areas of the network allowing the mine to operate efficiently with minimum interruptions.
The central cause of all this fuss is the extremely large population of bats living in the immediate vicinity. The electrical coordinator for the Sally Malay mine, Mr Peter Jensen, said the bats often swarm around the 11kV aerials causing faults.
“Some of them touch the metal crossarms creating a 300 Amp phase to ground fault”, he said.
“This would be picked up by the 11kV breaker at the power station which would open on an earth fault shutting down our underground and camp services”, he said.
The cost of running feeders underground for any significant length cannot be justified when a mine has an expected 5 - 10 year lifespan. On the other hand, the bats are protected and cannot simply be culled to reduce the problem. Kimberley Nickel Mines looked into the problem and decided to install two reclosers on the sections most affected by the bat strike problem.
“A bat strike downstream of the recloser opens on that particular aerial only, avoiding a complete outage, but also giving us an idea as to where to look for the offending bat”, said Peter.
Bats are usually incinerated when they come into contact with voltages of this level (11kV). When the recloser detects the fault it opens and lets the bat fall to the ground. This removes the fault and the reclose operation is generally successful.
The worst case now is that a small portion of the network may lose power while the fault is restored. In most cases, however, the interruption will only last a few seconds. A definite improvement by any measure.
Installation of the reclosers were undertaken by an electrical contractor. Peter Jensen, then contacted NOJA Power directly to help with commissioning. Although reclosers are a common sight in electrical utility networks, they are not so common in small privately owned networks.

NOJA Power pride themselves on superior service and support and are always ready to help customers who need to properly commission their new recloser. Due to the remote location of the mine, all training and commissioning advice was delivered over the phone and online using email.
NOJA Power's service manager. Oleg Samarski, was supplied Information on the substation circuit breaker settings, transformer sizes and other network Information. From this he calculated appropriate settings that accounted for proper protection coordination and transformer inrush currents.
"Commissioning a recloser as flexible as ours can be difficult if you have never worked with one before", said Oleg.
"We are always happy to help customers get the most out of our reclosers for their particular situation. In this situation we were able to solve a technical issue without the need to visit the site ourselves", he said.

After the recloser had been in service for a while the data log was downloaded and analysed. It was discovered that the recloser had cleared many temporary faults due to bat-strike. In order to reduce the number of interruptions, it was decided to further fine-tune the protection settings in order to coordinate the protection as close as possible with the main substation circuit breaker.
Reviewing the protection coordination based on actual in service data proved to be invaluable in improving the overall reliability of the power supply. The settings have now been adjusted so finely that interruptions have been reduced to the absolute minimum possible given the circumstances.
Peter Jensen also used the flexibility of the recloser to implement a fuse saving scheme and limit the effects of lightning and line slap.
“We set the reclosers so they will now open before we blow the Expulsion Drop Out fuses located on each aerial. We also have the recloser open and reclose in the event of a lightning strike or line slap”, he said.
“All this has helped us greatly and NOJA Power have been excellent with their backup service” he said.